Skip to Content

Leak Detection

Automatic Tank Gauging (ATG)

Probes in the tank are connected to a console containing electronics that monitor product levels. Precise product level readings are made in frequent intervals and a computer processes information and determines if preset conditions have been exceeded.

If preset conditions are exceeded, an alarm is triggered to alert tank owner/operator to possibility of a leak.

Many ATGs can be programmed to operate in monthly monitoring or tank tightness test modes. There are different performance standards for each method of operation. An ATG device in monthly monitoring mode must be able to detect a 0.2 gallon per hour leak from any part of the system which routinely contains product.

An ATG must be put into "leak check mode" once each month. When a tank is in "leak check mode" there must be no product put into or removed from the tank. Results of this test must indicate a "pass" or you may have an ongoing release.

Some ATGs are capable of doing "continuous" leak detection, meaning the operator does not have to put the system into leak check mode once per month. The software contained in this kind of program automatically makes the calculations based on there being enough "quiet time" where the tank is idle. Stations that operate 24 hours a day may find it difficult to collect enough quiet time. If that is the case, the tank owner must shut the tank down long enough for the system to collect the necessary data to determine if the tank is tight.

If you want to know more about Automatic Tank Gauging, EPA has a publication called Getting The Most Out Of Your Automatic Tank Gauging System.

Statistical Inventory Reconciliation (SIR)

This method is similar to inventory control. It differs from inventory control in that it is considered an acceptable form of monthly monitoring for tanks and piping* and does not have to be combined with a tightness test every five years.

Stick tank every day that it is in operation. Balance sales and deliveries for over and short.

Send records to SIR analyst who performs special statistical analysis with a computer.

Can be used to replace annual tank and line tightness testing.

If statistical analysis performed by SIR vendor is inconclusive for two (2) consecutive methods, report to State Division of UST a possible release and perform a tank tightness test.

*Use of SIR alone is not sufficient for Pressurized Piping. This requires a form of catastrophic leak detection such as Automatic Line Leak Detectors in addition to SIR.

If you want to know more about Statistical Inventory Reconciliation, the Division has a compliance Guidance Document entitled CGD 107 - SIR.

Interstitial Monitoring

This is a method of leak detection in which secondary containment is used and leak detection can be either between the walls of a double-walled tank or between the tank wall and secondary barrier or line in the tank pit excavation.

If a tank pit liner is used, it must not allow product to pass through and be constructed so that it directs any leaked product to a monitoring point.

Barriers must always be above groundwater and must not interfere with operation of the cathodic protection system if there is one in use.

If secondary containment is a created by a double wall tank, a variety of release detection devices can be used for monitoring this annular area.

If you want to know more about Interstitial Monitoring, the Division has a compliance Guidance Document entitled CGD 108 - Interstitial Monitoring.

New Interstitial Monitoring forms (These forms are in fillable Adobe format):

Annual Electronic Interstitial Monitoring (CN-1339)

Monthly Electronic Interstitial Monitoring (CN-1340)

Tank Tightness Testing

Tests system for leaks by closely monitoring changes in product level over a short period of time.

This test must be table to detect a leak of at least 0.1gallon per hour from tank while accounting for testing variables like product expansion or contraction, vapor products, tank deformation, water table level, etc.

Tennessee does not currently license, certify, or approve any particular testing methodology or tester, but only recognizes test methodology listed on the list published by the National Work Group on Leak Detection Evaluations. You can read or download this list at their website: http://www.nwglde.org/

If you want to know more about tank tightness testing, the Division has a compliance Guidance Document entitled CGD 112 - Tank and Line Tightness Testing.

Manual Tank Gauging

If a tank is 1000 gallons or less, and it can be left out of use for a specified period of time each week, this method can be used as a sole method of release detection.

It may also be used on tanks between 1001 and 2000 gallons provided it is combined with annual tank tightness testing.

See table below for tank sizes, diameters, time intervals which must be followed when using this method.

Method:

Take two stick readings at the beginning of the test.

Average these readings to establish a Beginning Level.

Wait correct amount of time before repeating this procedure.

Repeat sticking procedure and obtain two more readings.

Average these to determine the Ending Level.

Subtract the Ending Level from the Beginning Level and compare to the Weekly Standard below.

The result must be within the Weekly Standard to be considered tight.

Repeat this procedure each week.

Add all the weekly test results for one month and divide by the number of weeks in the month.

Compare this result to the Monthly Standard.

This result must be within the Monthly Standard to be considered tight.

Nominal Tank Capacity
(in gallons)
Tank Dimensions Weekly Standard
(in gallons)
Monthly Standard
(in gallons)
Minimum Test Duration
500 N/A 10 5 36 hours
551 - 1,000 N/A 13 7 36 hours
1,000 64" diameter x
73" length
9 4 44 hours
1,000 48" diameter x
128" length
12 6 58 hours
1,1001 - 2,000 N/A 26 13 36 hours

If you want to know more about Manual Tank Gauging, EPA has a publication called Manual Tank Gauging for Small Underground Storage Tanks.

Leak Detection For Piping

There are two kinds of product delivery piping: pressurized and suction. Suction piping operates at less than atmospheric pressure and is less likely to result in large releases than pressurized piping. Pressurized piping uses a pump submerged in the product and maintains a positive pressure on the product lines even when product is not being dispensed.

There are different leak detection requirements for each type of product delivery piping.

Any monthly method of leak detection can be used for piping if it can detect a release from piping with 30 days.

An annual line tightness test may be conducted on pressurized piping systems in lieu of monthly monitoring.

Automatic line leak detectors are required for pressurized piping. These are designed to interrupt the flow of product in the event of a catastrophic release. They must capable of detecting a release of 3 gallons per hour at 10 psi within 1 hour.

If you want to know more about piping leak detection requirements, the Division has two compliance Guidance Documents entitled CGD 110 - Pressurized Piping and CGD 111 - Suction Piping.

Leak Detection Recordkeeping

Keep all written performance claims, manufacturer's schedules of required maintenance, and systems calibration for 5 years from date of installation.

Keep results of all sampling, testing, or monitoring for 1 year. This includes tightness tests, inventory records, monthly test results, and monitoring well logs.

It is not sufficient to merely DO monthly leak detection. You must also be able to document that you have done the required monthly checks for leaks. This means keeping careful and complete records.